DCP-100
A1R point heat detector
The point heat detector is designed to detect a rapid rise in temperature or cases of exceeding the limit temperature as a result of a developing fire.
- A1R heat detector in conformance with EN54-5
- simple installation of the detector at the base of DB-100
- possibility of connecting an external status indicator
The actual appearance of the products may differ from the presented images. Product descriptions are provided in the web service for information purposes only.
Documentation
general information manual
updated: 2022-12-05
363 KB
Certificates
Other certificates
updated: 2022-11-22
1.80 MB
Declaration of performance
updated: 2022-11-22
611 KB
EU declaration of conformity
updated: 2024-06-21
116 KB
Technical Data
Enclosure dimensions
ø108 x 49 mm
Operating temperature range
-25...+50 °C
Supply voltage
10,5...26 V DC
Class according to EN 54-5 (heat sensor)
A1R
Minimum static response temperature
54 °C
Maximum static response temperature
65 °C
Current draw when detecting
0,022 mA
Current draw when emitting an alarm
23 mA
Information materials
3leaflet - installer
5product data sheet