DMP-100

Point heat and smoke multi-sensor detector

The point multi-sensor detector combines in a single device the functionality of visible smoke detection, the rate-of-rise detection and the detection of cases of exceeding the limit temperature. Owing to this combination of detection technologies, the DMP-100 detector can detect many different sources of fire.

  • unique Swirl chamber accelerates smoke detection
  • test fires detected: TF-1 to TF-5 acc. to EN54-7 and TF-1, TF-6 and TF-8 acc. to ISO/TS 7240-9:2006
  • A1R heat detector in conformance with EN54-5
  • stainless-steel precision filter
  • failure signalling – contamination of measuring chamber
  • simple detector installation at the base of DB-100
  • possibility of connecting an external status indicator
DMP-100
The actual appearance of the products may differ from the presented images. Product descriptions are provided in the web service for information purposes only.

Documentation

general information manual
updated: 2022-12-05
363 KB

Certificates

Other certificates
updated: 2022-11-22
2.92 MB
Declaration of performance
updated: 2022-11-22
846 KB
EU declaration of conformity
updated: 2024-06-21
115 KB

Technical Data

Enclosure dimensions
ø108 x 49 mm
Operating temperature range
-25...+50 °C
Supply voltage
10,5...26 V DC
Weight
94 g
Maximum humidity
93±3%
Class according to EN 54-5 (heat sensor)
A1R
Minimum static response temperature
54 °C
Maximum static response temperature
65 °C
Current draw when detecting
40 µA
Current draw when emitting an alarm
23 mA

Information materials

3leaflet - installer

5product data sheet

 © 1990-2021 SATEL sp. z o.o.
legal | privacy policy | Feedback | about site

The Satel.pl website uses cookies to enable Users' to take advantage of Satel.pl features as well as for statistical purposes. Unless you block cookies, you grant your consent for their use and storage in device memory. You must remember that you are able to manage cookies by means of your browser settings. Lack of adjustment of these settings means your consent for the Satel.pl website to use the cookies. See our Privacy Policy for more information.